Severity |
Error code |
Description |
Remedy |
|---|---|---|---|
|
2 |
8235 |
Internal error |
Replace module |
|
2 |
8448 |
Operation finished |
Change Safety PLC switch address setting or remove memory card from non-safety PLC. Restart Safety PLC. If this error persists, replace Safety PLC. |
|
2 |
8449 |
Wrong user data |
Delete user data from Safety PLC. Restart Safety PLC and write user data again. |
|
2 |
8450 |
Internal PROFIsafe initialization error |
Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support. |
|
2 |
8460 |
Flash read error |
Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support. |
|
2 |
8466 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8476 |
Boot project download error |
Reload boot project. If this error persists, replace Safety PLC. |
|
2 |
8488 |
Wrong firmware version |
Update Safety PLC firmware. Restart Safety PLC. If this error persists, replace Safety PLC. |
|
2 |
8491 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8496 |
Overvoltage or undervoltage detected |
Restart Safety PLC. Check Safety PLC setting for power supply error. If this error persists, replace Safety PLC. |
|
2 |
8500 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8704 |
User program triggered safe stop |
Check user program |
|
2 |
8705 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8706 |
Internal PROFIsafe error |
Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support. |
|
2 |
8707 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8714 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8717 |
Flash write error |
Restart Safety PLC. If this error persists, replace Safety PLC. Contact ABB technical support. |
|
2 |
8721 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8722 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8723 |
Checksum error has occured in Safety PLC |
Restart Safety PLC. If this error persists, replace Safety PLC. |
|
2 |
8729 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8741 |
Cycle time error in Safety PLC |
Check Safety PLC watchdog time. |
|
2 |
8742 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8746 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8747 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8756 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8758 |
Internal error |
Contact ABB technical support. Replace Safety PLC. |
|
2 |
8990 |
PROFIsafe configuration error |
Check F-Parameter configuration of I/O module and reload boot project |
|
3 |
12561 |
Safety source addresses cannot be checked |
Check PROFIsafe F-Host library version (2.0.0 or above). If this error persists, contact ABB technical support. |
|
3 |
12570 |
Error in configuration data, safety PLC has not accepted configuration data, e.g., mismatch between safety and non-safety PLC configuration. |
Create new configuration data for both safety and non-safety PLC again, re-create and download boot projects to both safety and non-safety PLC again. |
|
3 |
12571 |
Error in configuration data, Safety PLC cannot read configuration data |
Create boot project |
|
3 |
12598 |
PROFIsafe F_Dest_Add rules are violated |
Check Safety PLC configuration or switch address setting against PROFIsafe F_Dest_Add configuration rules. Restart Safety PLC. If this error persists, contact ABB technical support. |
|
3 |
32770 |
Watchdog error communication module |
|
|
3 |
32771 |
Wrong firmware version of communication module |
Update firmware |
|
3 |
32772 |
Initialisation of safety module on slot failed. More than one safety module plugged |
Remove this module or Only that one safety module plugged -> defective, replace this module |
|
3 |
32774 |
Invalid configuration data |
Check configuration |
|
3 |
32775 |
Safety module not found |
Check configuration. At Safety PLC: Check Safety PLC switch address setting. Restart Safety PLC. If this error persists, replace Safety PLC. |
|
3 |
32776 |
Safety module has wrong type |
Check configuration |
|
4 |
16640 |
Reserved switch address setting. |
Warning |
|
4 |
16644 |
Boot project not loaded, maximum power dip reached |
Restart Safety PLC |
|
4 |
16648 |
Power dip data missed or corrupted. Default power dip data was flashed by Safety PLC |
Warning |
|
4 |
16659 |
CRC error boot project |
Create new boot project and restart Safety PLC |
|
4 |
16909 |
Flash write error (production data) |
Warning |
|
4 |
16935 |
More than one instance of SF_WDOG_TIME_SET or SF_MAX_POWER_DIP_SET |
Warning |
|
4 |
16922 |
No or wrong configuration data from PM5x, run state not possible |
Create correct boot project at PM5x |
|
4 |
17421 |
Flash write error (boot project) |
Warning |
|
4 |
17677 |
Flash write error (boot code) |
Warning |
|
4 |
17933 |
Flash write error (firmware) |
Warning |
|
4 |
18189 |
Flash write error (password) |
Warning |
|
4 |
18445 |
Flash write error (user data) |
Warning |
|
4 |
18701 |
Flash write error (user data) |
Warning |
|
4 |
18957 |
Flash write error (internal) |
Warning |
|
4 |
19213 |
Flash write error (internal) |
Warning |
|
4 |
19469 |
Flash write error (internal) |
Warning |
|
4 |
32777 |
Program not started because of configuration error |
Check configuration |
|
4 |
32778 |
Program not started, no application running in safety module |
Check configuration, download safety application to safety module |
|
Severity |
Error code |
Description |
Remedy |
|---|---|---|---|
|
3 |
3 |
Discrepancy time expired |
Check discrepancy time value, channel wiring and sensor. |
|
3 |
12 |
Test pulse error |
Check wiring and sensor. |
|
3 |
13 |
Channel test pulse cross-talk error |
Check wiring and sensor. If this error persists, replace I/O module. Contact ABB technical support. |
|
3 |
25 |
Channel stuck-at error |
Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O module. |
|
3 |
28 |
Channel cross-talk error |
Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O module. |
|
3 |
260 |
Measurement overflow at the I/O module |
Check channel wiring and sensor power supply. |
|
3 |
263 |
Measurement underflow at the I/O module |
Check channel wiring and sensor power supply. |
|
3 |
311 |
Channel value difference too high |
Adjust tolerance window for channels. Check channel wiring and sensor configuration. |
|
3 |
525 |
Channel readback error |
Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O module. |
|
3 |
530 |
Channel cross-talk error |
Check I/O module wiring. Restart I/O module, if needed. If this error persists, replace I/O module. |
|
3 |
16138 |
Process voltage too high |
Check process voltage |
|
3 |
16139 |
Process voltage too low |
Check process voltage |
|
3 |
16148 |
PROFIsafe communication error |
Restart I/O module. If this error persists, contact ABB technical support. |
|
3 |
16153 |
PROFIsafe watchdog timed out. |
Restart I/O module. If this error persists, increase PROFIsafe watchdog time. |
|
3 |
16171 |
Internal error in the device |
Replace I/O module |
|
Severity |
Error code |
Description |
Remedy |
|---|---|---|---|
|
3 |
16146 |
Plausibility check failed (iParameter) |
Check configuration |
|
3 |
16147 |
Checksum error in the I/O module |
Check safety configuration and CRCs for I- and F-Parameters. |
|
3 |
16154 |
Parameter value |
Check master or configuration |
|
3 |
16156 |
F-Parameter configuration and address switch value do not match. |
Check I/O module F-Parameter configuration and module address switch value. |