The system data of AC500 and S500 is applicable to the standard version.⮫ “System data AC500”
The system data of AC500-XC is applicable to the XC version.⮫ “System data AC500-XC”
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Processor module and terminal base
|
Parameter |
Value |
|---|---|
|
Connection of the supply voltage 24 V DC at the terminal base of the processor module |
Removable 5-pin terminal block with spring connection |
|
Current consumption on 24 V DC |
|
|
Min. typ. (module alone) |
PM5630-2ETH: 110 mA PM5650-2ETH: 120 mA PM5670-2ETH: 140 mA PM5675-2ETH: 140 mA PM5680-2ETH: 160 mA PM5685-2ETH: 160 mA |
|
Max. typ. (all communication modules and I/Os) |
PM5630-2ETH: 400 mA PM5650-2ETH: 600 mA PM5670-2ETH: 800 mA PM5675-2ETH: 800 mA PM5680-2ETH: 800 mA PM5685-2ETH: 800 mA |
|
Number of slots for processor modules |
1 (on all terminal bases) |
|
Processor module interfaces at the terminal bases TB56xx |
I/O bus, ETH1, ETH2, CAN, COM1 |
|
Weight (processor module without terminal base) |
135 g |
|
Mounting position |
Horizontal or vertical |
|
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 |
PM5685 |
|
|---|---|---|---|---|---|---|---|
|
Total maximum downloadable application size 1) |
9 MB |
84 MB |
176 MB |
176 MB |
176 MB |
320 MB |
|
|
Thereof user program code and data (dynamically allocated) |
2 MB |
8 MB |
32 MB |
32 MB |
32 MB |
64 MB |
|
|
Thereof user webserver data max. |
6 MB |
72 MB |
128 MB |
128 MB |
128 MB |
256 MB |
|
|
Flash memory for User data |
|||||||
|
Remaining for all other usage (project save, infrastructure...) |
40 MB |
380 MB |
850 MB |
850 MB |
850 MB |
850 MB |
|
|
Buffered (SRAM) |
256 kB |
256 kB |
1.5 MB |
1.5 MB |
1.5 MB |
1.5 MB |
|
|
Thereof VAR retain persistent |
128 kB |
128 kB |
1024 kB |
1024 kB |
1024 kB |
1024 kB |
|
|
Thereof %M memory (e.g. Modbus register) |
128 kB |
128 kB |
512 kB |
512 kB |
512 kB |
512 kB |
|
|
Expandable memory |
None |
None |
None |
None |
None |
None |
|
|
Integrated mass storage memory (FLASH) |
None |
None |
None |
8 GB |
None |
None |
|
|
Slot for pluggable memory card |
x |
x |
x |
x |
x |
x |
|
|
Processor type |
TI ARM Cortex-A9 32-bit-RISC |
Multi-Core ARM Cortex-A53 64-bit |
|||||
|
Processor clock speed |
300 MHz |
600 MHz |
1 GHz |
1 GHz |
1 GHz |
1 GHz |
|
|
Cycle time for 1 instruction (minimum): |
|||||||
|
Binary |
Min. 0.02 µs |
Min. 0.01 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
|
|
Word |
Min. 0.02 µs |
Min. 0.01 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
|
|
Floating point |
Min. 0.12 µs |
Min. 0.01 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
Min. 0.002 µs |
|
|
Mathematic co-processor |
x |
x |
x |
x |
x |
x |
|
|
Motion capability |
|||||||
|
No. synchronized axis per 1 ms on EtherCAT CM typically |
- |
8* |
16* |
16* |
16* |
16* |
|
|
No. synchronized axis per 2 ms on EtherCAT CM typically |
4* |
16* |
32* |
32* |
32* |
32* |
|
|
No. synchronized axis per 4 ms on EtherCAT CM or CANopen onboard typically |
8* |
32* |
64* |
64* |
64* |
64* |
|
|
Min. bus cycle time for EtherCAT using external CM579 |
2 ms |
1 ms |
0,5 ms |
0,5 ms |
0,5 ms |
0,5 ms |
|
|
* in addition: 1 virtual axis |
|||||||
|
Max. number of central inputs and outputs (10 exp. modules): |
|||||||
|
Digital inputs |
320 |
||||||
|
Digital outputs |
320 |
||||||
|
Analog inputs |
160 |
||||||
|
Analog outputs |
160 |
||||||
|
Number of decentralized inputs and outputs |
Depends on the used fieldbus |
||||||
|
Data backup |
Battery |
||||||
|
Data buffering time at 25 °C |
Typ. 3 years |
||||||
|
Battery low indication |
via application program |
||||||
|
Real-time clock: |
|||||||
|
With battery backup |
x |
||||||
|
Accuracy |
Typ. ± 2 s / day at +25 °C |
||||||
|
Program execution: |
|||||||
|
Cyclic |
x |
||||||
|
Time-controlled |
x |
||||||
|
Multitasking |
x |
||||||
|
Minimum cycle time configurable for cyclical task |
1 ms |
1 ms |
0,5 ms |
0,5 ms |
0,5 ms |
0,5 ms |
|
|
User program protection by password |
x (user management) |
||||||
|
Internal interfaces for communication: |
|||||||
|
Serial interface COM1: |
|||||||
|
Physical link |
Configurable for RS-232 or RS-485 (9.6 kb/s, 19.2 kb/s, 38.4 kb/s, 57.6 kb/s and 115.2 kb/s) |
||||||
|
Connection |
Pluggable terminal block, spring connection |
||||||
|
Usage |
Serial ASCII communication,Modbus RTU |
||||||
|
CAN interface: |
|||||||
|
Physical link |
CAN 2A/2B (from 50 kb/s to 1 Mb/s) |
||||||
|
Connection |
Pluggable terminal block, spring connection |
||||||
|
Usage |
CANopen master communication, CAN 2A/2B, J1939 protocol, CAN sync |
||||||
|
Max. number of variables allowed |
|||||||
|
Input variables |
2 kB |
4 kB |
5 kB |
5 kB |
5 kB |
5 kB |
|
|
Output variables |
2 kB |
4 kB |
5 kB |
5 kB |
5 kB |
5 kB |
|
|
Network interface ETH1, ETH2: |
|||||||
|
Usage |
Ethernet |
||||||
|
Physical link |
10/100 base-TX, configurable as internal switch or independent Interfaces |
||||||
|
Connection |
2x RJ45 socket, provided on TB56xx-2ETH |
||||||
|
LEDs, LCD display, function keys |
RUN / STOP, status, diagnosis, settings |
||||||
|
Number of timers |
Unlimited |
||||||
|
Number of counters |
Unlimited |
||||||
|
Programming languages: |
|||||||
|
Structured Text ST |
x |
||||||
|
Instruction list IL |
x |
||||||
|
Function Block Diagram FBD |
x |
||||||
|
Ladder Diagram LD |
x |
||||||
|
Sequential function chart SFC |
x |
||||||
|
Continuous function chart (CFC) |
x |
||||||
|
Remarks: 1) The values are for information only and cannot be fulfilled altogether. The available resources are limited at the end by the maximal downloadable application size for each CPU. |
|
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 2) |
PM5685 2) |
|---|---|---|---|---|---|---|
|
TB5600-2ETH |
0 slot |
0 slot |
0 slot |
0 slot |
0 slot |
0 slot |
|
TB5610-2ETH |
1 slot |
1 slot |
1 slot |
1 slot |
1 slot |
1 slot |
|
TB5620-2ETH |
2 slots |
2 slots |
2 slots |
2 slots |
2 slots |
2 slots |
|
TB5640-2ETH |
- |
4 slots |
4 slots |
4 slots |
4 slots |
4 slots |
|
TB5660-2ETH |
- |
- |
6 slots 1) |
6 slots 1) |
- |
6 slots |
|
Remarks: The slots can be used for connecting communication modules or AC500-S modules. Note that only one AC500-S module can be connected at one terminal base. 1) PM567x must have the order numbers 1SAP151000R0378, 1SAP151500R0378 or a production index ≥ C0. 2) XC variant is not applicable. |
||||||
|
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 |
PM5685 |
|
|---|---|---|---|---|---|---|---|
|
Max. number of variables allowed for each communication module supported |
|||||||
|
Input variables |
4 kB |
4 kB |
5 kB |
5 kB |
5 kB |
5 kB |
|
|
Output variables |
4 kB |
4 kB |
5 kB |
5 kB |
5 kB |
5 kB |
|
|
Type of communication module supported |
|||||||
|
CM5610-2RS - 2 serial interfaces |
x |
x |
x |
x |
x |
x |
|
|
CM582-DP - PROFIBUS DP V0/V1 slave |
x |
x |
x |
x |
x |
x |
|
|
CM592-DP - PROFIBUS DP V0/V1 master |
x |
x |
x |
x |
x |
x |
|
|
CM579-ETHCAT - EtherCAT master |
x |
x |
x |
x |
x |
x |
|
|
CM579-PNIO - PROFINET IO RT controller |
x |
x |
x |
x |
x |
x |
|
|
CM589-PNIO - PROFINET IO RT device |
x |
x |
x |
x |
x |
x |
|
|
CM589-PNIO-4 - PROFINET IO RT |
x |
x |
x |
x |
x |
x |
|
|
CM5640-2ETH - 2 Ethernet interfaces |
x |
x |
x |
x |
x |
x |
|
|
CM598-CN - CAN, CANopen master |
x |
x |
x |
x |
x |
x |
|
|
Type of AC500-S module supported |
|||||||
|
SM560-S - safety module |
x |
x |
x |
x |
x |
x |
|
|
SM560-S-FD-1 - safety module with |
x |
x |
x |
x |
x |
x |
|
|
SM560-S -FD-4 - safety module with |
x |
x |
x |
x |
x |
x |
|
Communication and onboard protocols
|
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 |
PM5685 |
|
|---|---|---|---|---|---|---|---|
|
OPC UA server1) |
x |
x |
x |
x |
x |
x |
|
|
Number of free tags |
3.000 |
10.000 |
30.000 |
30.000 |
30.000 |
60.000 |
|
|
Number of connections |
10 |
20 |
50 |
50 |
50 |
100 |
|
|
Min. sampling rate (limit) |
500 ms |
100 ms |
50 ms |
50 ms |
50 ms |
50 ms |
|
|
OPC DA server AE |
x |
x |
x |
x |
x |
x |
|
|
Number of connections |
8 |
8 |
8 |
8 |
8 |
8 |
|
|
Remarks: 1) Maximum number of free tags using arrays. |
|||||||
|
Processor module |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 |
PM5685 |
||||
|---|---|---|---|---|---|---|---|---|---|---|
|
Modbus TCP client / server |
x |
x |
x |
x |
x |
x |
||||
|
Number of Modbus clients ModMast in parallel on a CPU master (server) |
30 |
50 |
120 |
120 |
120 |
300 |
||||
|
Number of Modbus server in parallel (e.g. for SCADA access) |
15 |
25 |
50 |
50 |
50 |
250 |
||||
|
IEC 60870-5-104 telecontrol protocol |
x |
x |
x |
x |
- |
x |
||||
|
Number of free tags |
1.000 |
5.000 |
10.000 |
10.000 |
- |
20.000 |
||||
|
Control station (number of connections) |
5 |
10 |
20 |
20 |
- |
40 |
||||
|
Sub-station (number of connections) |
5 |
10 |
20 |
20 |
- |
40 |
||||
|
DNP3 Outstation |
PM5630 |
PM5650 |
PM5670 |
PM5675 |
PM5680 |
PM5685 |
|---|---|---|---|---|---|---|
|
Number of tags |
1000 |
3000 |
10000 |
10000 |
- |
15000 |
|
Number of clients |
8 |
8 |
8 |
8 |
- |
8 |
|
Maximum number of events buffering |
200000 |
350000 |
800000 |
800000 |
- |
800000 |